High Performance MCB
The S803N-D8 is a 3-pole High Performance Circuit breaker with D-Characteristic, with cage terminal and a rated current of 8 A. It is a current limiting device with a maximum breaking capacity of 36kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S803N-D8 complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S803N-D8 more comfortable. Due to the fast arc extinction of S803N-D8 your application will be secured.
Ürün kimlikleri
SKU: 2CCS893001R0081
EAN: 7612271411749
GTIN: 7612271411749
MPN: S803N-D8
Kategoriler
Özellikler
|
EFI00218
|
3.248025
|
|
EFI07337
|
0|0.1085
|
|
EFI07343
|
0|0.0775
|
|
EFI07515
|
-13|140
|
|
Frequency
|
50 - 60 Hz
|
|
Voltage type
|
Other
|
|
Rated current
|
8 A
|
|
Rated voltage
|
400 V
|
|
Built-in depth
|
82.5 mm
|
|
Explosion-proof
|
hayır
|
|
Pollution degree
|
3
|
|
Over voltage category
|
4
|
|
Current limiting class
|
3
|
|
Release characteristic
|
D
|
|
Number of poles (total)
|
3
|
|
Degree of protection (IP)
|
IP20
|
|
Number of protected poles
|
3
|
|
Flush-mounted installation
|
hayır
|
|
Rated insulation voltage Ui
|
690 V
|
|
Additional equipment possible
|
evet
|
|
Width in number of modular spacings
|
4.5
|
|
Ambient temperature during operating
|
-25 - 60 °C
|
|
Rated impulse withstand voltage Uimp
|
8 kV
|
|
Concurrently switching neutral conductor
|
hayır
|
|
Connectable conductor cross section solid-core
|
|
|
Connectable conductor cross section multi-wired
|
|
|
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
|
-
|
|
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
|
20 kA
|
|
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
|
-
|
|
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
|
36 kA
|