Type1+2+3 combined arrester DEHNshield ZP Basic 2 for TNC systems
Tested type 1 + type 2 + type 3 combined arrester according to IEC 61643-11 for TN-C systems (3+0 configuration) including overcurrent-protected 230 V power supply (N and L) including spare fuse for the compartment for additional applications / termination point meter mounting board according to VDE-AR-N 4100; can be installed completely without tools thanks to click + power connection method for 40 mm busbar systems and push-in earthing terminal; for use in the main power supply system according to IEC 60634-4-44 clause 443 of buildings without a lightning protection system (also in case of overhead line supply). A suitable cover clip according to DIN VDE 0603-1 for every standard meter panel and 2 x socket and 2 x plug (without connecting cables) for wiring the intelligent measuring system according to VDE-AR 4100 are included in delivery.
Ürün kimlikleri
SKU: 909430
EAN: 4013364409842
GTIN: 4013364409842
MPN: DSH ZP B2 SG TNC 255
Kategoriler
Özellikler
|
Test class
|
Type 1 and 2 and 3
|
|
Max. PV-voltage
|
-
|
|
Mounting method
|
Busbar
|
|
Number of poles
|
3
|
|
Construction size
|
-
|
|
Remote signalling
|
-
|
|
Nominal voltage AC
|
230 V
|
|
Nominal voltage DC
|
-
|
|
Specific energy (W/R)
|
14.06 kJ/Ohm
|
|
Integrated backup fuse
|
-
|
|
System configuration DC
|
-
|
|
System configuration IT
|
-
|
|
System configuration TN
|
-
|
|
System configuration TT
|
hayır
|
|
Signalling at the device
|
Optical
|
|
Voltage protection level
|
1.5 kV
|
|
Degree of protection (IP)
|
IP30
|
|
System configuration TN-C
|
evet
|
|
System configuration TN-S
|
hayır
|
|
Max. continuous voltage AC
|
255 V
|
|
Max. continuous voltage DC
|
-
|
|
System configuration other
|
-
|
|
System configuration TN-C-S
|
hayır
|
|
Voltage protection level L-N
|
-
|
|
Voltage protection level L-PE
|
-
|
|
Voltage protection level N-PE
|
-
|
|
Voltage protection level (DC+ - DC-)
|
-
|
|
Overcurrent protected voltage tapping
|
evet
|
|
Lightning impulse current (10/350 µs)
|
22.5 kA
|
|
Voltage switching spark gap technology
|
evet
|
|
Follow current extinguishing capability
|
25 kA
|
|
Voltage protection level (DC+/DC- - PE)
|
-
|
|
Max. conductor cross section flexible (fine-strand)
|
-
|
|
Max. conductor cross section solid (solid, stranded)
|
25 mm²
|
|
Max. overcurrent protection device, series connection (fuse)
|
160 A
|
|
Max. overcurrent protection device, parallel connection (fuse)
|
160 A
|
|
Energy-coordinated protection effect with regard to the terminal equipment
|
evet
|