Type 2+3 surge arrester DEHNcord 3-phase for electr. inst. systems

Type 2+3 surge arrester DEHNcord 3-phase for electr. inst. systems

Three-phase DEHNcord type 2 + type 3 surge arrester according to EN 61643-11 with a compact design for all installation systems; mounted on DIN rails or, in confined spaces, using screw lugs. For installation in conformity with the lightning protection zone concept at the boundaries from 0B – 1 and higher.

Ürün kimlikleri

SKU: 900439
EAN: 4013364436053
GTIN: 4013364436053
MPN: DCOR 3P TT 275 FM

Kategoriler

Özellikler

Category type 2
evet
Max. PV-voltage
-
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
-
Nominal voltage AC
230 V
Nominal voltage DC
-
Leakage-current free
-
Integrated backup fuse
-
System configuration DC
-
System configuration IT
-
System configuration TN
-
System configuration TT
evet
Signalling at the device
Optical
Voltage protection level
-
Degree of protection (IP)
IP20
System configuration TN-C
-
System configuration TN-S
evet
Max. continuous voltage AC
275 V
Max. continuous voltage DC
350 V
System configuration other
-
System configuration TN-C-S
-
Voltage protection level L-N
1.5 kV
Voltage protection level N-PE
1.5 kV
With remote signalling contact
evet
Integrated short-circuit protection
-
Max. discharge surge current (8/20)
20 kA
Nominal discharge surge current (8/20)
10 kA
Number of conductors (without earthing)
4
Short-circuit breaking capacity (Isccr)
6 kA
Max. conductor cross section flexible (fine-strand)
6 mm²
Max. conductor cross section solid (solid, stranded)
6 mm²
Integrated short-circuit protection selective to fuse gG
-
Max. overcurrent protection device, series connection (fuse)
25 A
Max. overcurrent protection device, parallel connection (fuse)
40 A