C.BREAKER TMAX T8V 3200 FIXED THREE-POLE WITH TERMINALS REAR VERTICAL AND SOLID-STATE RELEASE IN AC PR331/P-LSIG R 3200

Teknik özellikler

Rated voltage 690 - 690 V
Number of poles 3
Device construction Built-in device fixed built-in technique
Motor drive optional evet
Motor drive integrated hayır
Type of control element Toggle
Degree of protection (IP) IP20
Rated permanent current Iu 3200 A
Overload release current setting 1280.0 - 3200 A
Complete device with protection unit evet
DIN rail (top hat rail) mounting optional hayır
Type of electrical connection of main circuit Bolt connection
Adjustment range undelayed short-circuit release 4800.0 - 38400 A
Number of auxiliary contacts as normally open contact
Adjustment range short-term delayed short-circuit release 1920.0 - 32000 A