Distribütör Seçimi

Alışveriş sepetiniz için kullanmak istediğiniz distribütörü seçin.

Distribütör

Appl.-opt. combined arrester DEHNshield type 1+2 for single-phase TT a. TN systems Zoomed Image
DEHN

Appl.-opt. combined arrester DEHNshield type 1+2 for single-phase TT a. TN systems

Application-optimised multipole type 1 and type 2 spark-gap-based combined lightning current and surge arrester according to EN 61643-11. Compact design due to space-saving spark gap technology with a width of only 1 module / pole. For use in residential buildings and special applications. Capable of protecting terminal equipment. For protecting low-voltage consumer's installations against surges, even in case of direct lightning strikes. For installation in conformity with the lightning protection zone concept at the boundaries from 0A – 2.

Ürün detayları

SKU Kodu: 941110

EAN Kodu: 4013364137899

Minimum sipariş: 1

Teknik Veriler

Ana Özellikler

Mounting method

DIN rail (top hat rail) 35 mm

Lightning impulse current (10/350 µs)

25 kA

Number of poles

2

Construction size

2 modular spacing

Voltage protection level

-

Remote signalling

hayır

Follow current extinguishing capability

25 kA

Max. continuous voltage AC

255 V

Nominal voltage AC

230 V

Nominal voltage DC

-

Test class

Type 1 + 2

Voltage protection level L-N

1.5 kV

Signalling at the device

Optical

Max. continuous voltage DC

-

Degree of protection (IP)

IP20

Max. PV-voltage

-

Voltage protection level N-PE

1.5 kV

Integrated backup fuse

-

Max. conductor cross section solid (solid, stranded)

35 mm²

Max. conductor cross section flexible (fine-strand)

25 mm²

Voltage protection level (DC+ - DC-)

-

Voltage protection level (DC+/DC- - PE)

-

Specific energy (W/R)

156.25 kJ/Ohm

Energy-coordinated protection effect with regard to the terminal equipment

evet

System configuration DC

-

System configuration IT

-

System configuration TN

evet

System configuration TN-C

-

System configuration TN-S

-

System configuration TT

evet

System configuration other

-

System configuration TN-C-S

-

Voltage protection level L-PE

-

Max. overcurrent protection device, parallel connection (fuse)

160 A

Max. overcurrent protection device, series connection (fuse)

100 A

Voltage switching spark gap technology

evet

Overcurrent protected voltage tapping

-

İndirilenler